DESIGN, CONSTRUCTION AND TESTING OF A COLD STORE WITH WATER-COOLED CHILLER
DOI:
https://doi.org/10.52292/j.laar.2022.635Keywords:
cold store, chiller, design, heat loadAbstract
Objective of this research was to design, construction and test of a cold store with chiller unit. Dimensions of the cold store were 5x4x3m. Heat load was calculated and capacity of cooling system was determined. Ambient temperature was set 2oC and relative humidity 90% for cold store testing. Ambient temperature, relative humidity and air velocity were measured for 3 different levels and 12 points for each level in the cold store. Total heat load and capacity of cooling system were calculated 5222 kcal/h. and 6.07 kW respectively. The descriptive statistics were calculated for the ambient temperature; mean, 2.82oC, standard deviation 0.02oC and CV(%) 0.56, and for the relative humidity; mean 88.01%, standard deviation 0.61 (%) and CV(%) 0.70 and for the air velocity mean 0.37m/s, standard deviation 0.22 m/s, CV 33.45 %. Even the air velocity CV was high, the ambient temperature and relative humidity variations were evaluated very good.
Published
Issue
Section
License
Copyright (c) 2022 Latin American Applied Research - An international journal
This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Once a paper is accepted for publication, the author is assumed to have transferred its copyright to the Publisher. The Publisher will not, however, put any limitation on the personal freedom of the author to use material from the paper in other publications. From September 2019 it is required that authors explicitly sign a copyright release form before their paper gets published. The Author Copyright Release form can be found here